Outputs; Timers - Deif SGC 110 User Manual

Single genset controller
Table of Contents

Advertisement

Level 2
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
(LOP) Circuit Fault Action
(OPEN CKT ALARM)
(LOP) Lube Oil Pressure Sensor Calibration

6.2.5 Outputs

Table 6.7
Outputs # (OUT #)
Level 2
Source
(SOURCE)
On Activation
(ON ACTIVATION)

6.2.6 Timers

Table 6.8
Cranking (CRANKING TIMERS)
Level 2
Crank Hold Time
(CRANK HOLD TIME)
Crank Rest Time
(CRANK REST TIME)
Manual Start Delay
(MANUAL START DELAY)
Auto Start Delay
(AUTO START DELAY)
Table 6.9
General (GENERAL TIMER)
Level 2
Safety Monitoring Delay
(SAFETY MONITOR DELAY)
Mains Detect Delay
(MAINS DETECT DELAY)
Alternator Detect Delay
(ALT DETECT DELAY)
Warm-Up Delay
(WARM-UP DELAY)
Return To Mains Delay
(RETN-TO-MAINS DELAY)
Engine Cooling Time
(ENG COOL TIME)
USER MANUAL 4189341228A UK
Range
1 to 60 s
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 10 to 100 Ω
Pressure: 1.0 to 10.0 bar
Range
See Digital output source selection in this document
Energise
De-energise
Range
1 to 15 s
2 to 60 s
0 to 300 s
0 to 43200 s
Range
10 to 60 s
N/A
1 to 30 s
0 to 60 s
N/A
0 to 300 s
Page 21 of 34

Advertisement

Table of Contents
loading

Table of Contents