11.
Accessories
Tab. 11.1 Optionally available accessories
Optionally available accessories
KHS-VAV with servo drive 230 V
KHS-VAV plus with spring-reset servo drive (230 V)
KHS drain with overflow monitor
KHS temperature sensor fitting PT 1000
KHS flow measurement valve
Leakage water sensor
12.
Wiring instructions for components with electrical connection
Tab. 12.1 Wiring instructions for components with electrical connection
Designation
KHS-VAV plus maximum flow
isolating ball valve with spring-reset
servo drive (230 V)
KHS-VAV maximum flow isolating
ball valve with servo drive (230 V)
KHS drain with overflow monitor
Kemper Control-plus
Flow measurement valve Vortex
principle
KHS temperature sensor fitting PT
1000
CAN bus cable'***
The application is based on the ISO
11898 international standard.
Leakage water sensor
*
Possible cable type for fixed routing
** Shielded cable supply lin
*** (To be provided by construction site)
Manual KHS Mini System Control
For KEMPER
order no.
68605015 032
69605015
68604015 032
69604015
68800020...032
6384G015 025
1384G015 050
6280G015...050
6290G015...050
1 x 2 x 0.25² ... 0.34²
68602005
1 x 2 x 0.34² ... 0.5²
68602006
1 x 2 x 0.50² ... 0.6²
1 x 2 x 0.75² ... 0.8²
6200000100
2x0.75²
e
82
FIGURE
686 04
686 05
688 00
628 0G / 629 0G
638 4G / 138 4G
620 00 001
Cable cross-
Max. cable
section
length
mm²
m
3 x 1.5²
9500
4 x 1.5²
9500
2 x 0.25²
150
7 x 0.34² **
300
4 x 2 x 0.6
10,000
0 m
40 m
300 m
500 m
0-50
50-500
Cable type*
NYM-J 3 x 1.5mm²
NYM-J 4 x 1.5mm²
J-Y(ST)Y 1x2x0.6mm²
or NYM-J 3x1.5mm²
J-Y(ST)Y 4x2x0.6mm²
J-Y(ST)Y 4x2x0.6mm²
40 m
300 m
CAN bus cable
600 m
1000 m
Standard cable
UL-LIYCY
Version: 21/11/2013