Routine duration
If there is no temperature flushing within the configured interval, the water exchange is guaranteed
through the "Routine duration" operating mode. To accomplish that, the decisive interval (max. 168 h)
and the duration of the water exchange can be stored in the "Routine duration" operating mode.
Illustration 8.43 shows the individual steps for configuration.
Ill. 8.43 Configuration of routine duration
Routine volume
If there is no temperature flushing within the configured interval, the water exchange is guaranteed
through the "Routine volume" operating mode. To accomplish that, the decisive interval (max. 168 h),
the volume and the maximum flushing time of the water exchange can be stored in the "Routine
volume" operating mode.
Illustration 8.44 shows the individual steps for configuration.
Ill. 8.44 Configuration of routine volume
Note:
After successfully configuring your system controls, it is recommended to save the
configuration as a backup file. If the KHS Mini System Control -MASTER 2.0- is
defective it can be quickly replaced and the configuration can be read in. That
saves having to configure everything again.