Appendix B: Power Supply and Battery Calculations

Model Number
Main Chassis (12 Amp)
FX-2003-12NDS
FX-2017-12NDS
Main Chassis (12 Amp)
FX-2009-12NDS
Large Main Chassis (12 Amp)
ALCN-792M
Dual Analog Loops
ALCN-792M/D
Quad Analog Loops
FNC-2000
Fire Network Controller Module
ANC-5000
Audio Network Controller Module
Telephone Network Controller
TNC-5000
Module
FOM-2000-SP
Fiber Optics Module
DM-1008A
8 Initiating Circuit Module
SGM-1004A
4 Indicating Circuit Module
RM-1008A
8 Relay Circuit Module
FDX-008/KI
Fan Damper Control Module
DSPL-420
Narrow Display
DSPL-2440
Graphic Display
UDACT-300A
Dialer Module
PR-300
City Tie Module
FDS-008
Selection Control Panel for MNS
RAX-1048TZDS
Adder Annunciator Chassis
RAM-1032TZDS
Adder Annunciator Chassis
AGD-048
Adder Graphic Driver Board
IPS-2424DS
Programmable Input Switches Module
Two-Wire Smoke Detectors
MIX-1251B/BA Analog Ion Smoke Detector
MIX-2251B/BA Analog Photo Smoke Detector
MIX-2251TMB/TMBA Analog Thermal Sensor
MIX-M500MB/MA, MIX-M501MB/MA Monitor
MIX-M500R(A)/MIX-M500S(A) Addressable Control Module
MIX-M500X(A) Fault Isolator Module
B224BI(A) Analog Base with Isolator
Four-Wire Smoke Detectors
Signal Load (bells, horns, strobes, and etc.)
Auxiliary Power Supply for Remote Annunciators
Total currents (Add above currents)
Battery Calculations continued. . . .
Power Requirements (All currents are in amperes)
Description
Qty
FleX-Net
Total
Standby
Standby
X
0.310
=
X
0.310
=
X
0.310
=
X
0.130
=
X
0.130
=
X
0.190
=
X
0.255
=
X
0.195
=
X
0.015
=
X
0.080
=
X
0.060
=
X
0.025
=
X
0.015
=
X
0.025
=
X
0.029
=
X
0.045
=
X
0.035
=
X
0.024
=
X
0.022
=
X
0.050
=
X
0.035
=
X
0.010/0.005
=
X
=
0.00005
X
0.0003
=
X
0.0003
=
X
0.0003
=
X
0.0004
=
X
0.0003
=
X
0.00045
=
X
0.00045
=
X
=
X
=
STANDBY
(A)
TM
Installation and Operation Manual
Total
Alarm
Alarm
0.733
=
0.733
=
0.733
=
0.145
=
0.145
=
0.190
=
0.265
=
0.215
=
0.015
=
1 zone active: 0.125
2 zone active: 0.170
4 zone active: 0.275
=
6 zone active: 0.370
8 zone active: 0.465
0.258
=
0.150
=
0.035
=
0.025
=
0.035
=
0.120
=
0.300
=
0.112
=
1 zone active: 0.026
2 zone active: 0.030
3 zone active: 0.035
=
4 zone active: 0.039
48 zone active: 0.262
32 zone active: 0.300
=
__(#of LEDs) x 4mA
=
(Refer to LT-847 if using
lamps)
0.015/0.022
=
*
0.39
= 0.39
0.0065
=
0.0065
=
0.0065
=
0.0051/0.0055
=
0.0051
=
450μA
=
0.005
=
=
=
=
Alarm
(B)
123