WAGO 2789-9080 Product Manual page 20

Communication modules, communication module io-link
Hide thumbs Also See for 2789-9080:
Table of Contents

Advertisement

Fieldbus Description
In-
Sub
dex
inde
x
393 0
394 0
395 0
404 0
405 0
424 0
432 0
20
| Version: 1.1.0
Communication Module IO-Link
Param-
Access
Data type Data
eter
Over-
read/write UIntegerT Yes
load
warning
thresh-
old
Output
read/write UIntegerT Yes
Behav-
ior
Switch-
read/write UIntegerT Yes
on de-
lay
Trip
read/write UIntegerT Yes
current
Trip de-
read/write UIntegerT Yes
lay
Signali-
read/write UIntegerT No
sation
Config-
uration
of digi-
tal input
Signali-
read/write UIntegerT No
sation
Config-
uration
of digi-
tal out-
put
Default set-
Range
Storage
ting
2.5 A: 0 mA
0 ... 2500 mA
5 A: 0 mA
0 ... 5000 mA
10 A: 0 mA
0 ...10000 mA
15 A: 0 mA
0 ...15000 mA
20 A: 0 mA
0 ...20000 mA
40 A: 0 mA
0 ...40000 mA
0 ms
0 ... 60000 ms
2,5 A:
250 ...
2500 mA
2500 mA
5 A:
500 ...
5000 mA
5000 mA
10 A:
1000 ...
10000 mA
10000 mA
15 A:
1500 ...
15000 mA
15000 mA
20 A:
2000 ...
20000 mA
20000 mA
40 A:
4000 ...
40000 mA
40000 mA
100 ms
100 ...
60000 ms
2789-9080
Data
Description
length
(Bytes)
2
Overload threshold
between > 0 A and
rated current.
2
Behavior settings
(for options
see8 Output be-
havior (Index 394)
[} 23])
2
User-configurable
switch-on delay
(waiting time be-
tween AC mains
voltage is applied,
i.e., the processor
has booted and
power stages are
switched on).
2
User-configurable
threshold between
10 % of rated cur-
rent and rated cur-
rent.
2
Circuit breaker fun-
tion:
User-configurable
time how long an
overcurrent is ig-
nored.
100 ... 60000 ms
2
Digital input be-
havior settings (for
options see
8 Configuration
of digital input
(Index 424)
[} 24])
2
Digital output be-
havior settings (for
options see
8 Configuration
of digital output
(Index 432)
[} 25])

Advertisement

Table of Contents
loading

Table of Contents