3.9.5.1

Internal Status Messages and Arguments

Status
Message
0x00
0x01
0x01
0x01
0x01
0x01
0x01
0x01
0x01
0x01
0x02
0x07
3.9.5.2

Internal Bus Status Messages and Arguments

Status
Message
0x43
0x44
0x44
0x45
WAGO-I/O-SYSTEM 750
Bus System
Programmable Field Bus Controller 750-833
Status
Description
Argument
0x00
No fault
0x00
EEPROM check sum fault / check sum fault in the flash
parameter area
0x01
Overflow inline code buffer
0x02
Unknown data type
0x03
Module type for flash program memory could not be
determined / is incorrect
0x04
Fault when writing in the FLASH memory
0x05
Fault when deleting the FLASH memory
0x06
Changed I/O modules configuration determined after
AUTORESET
0x07
Fault when writing in the serial EEPROM
0x08
Invalid firmware
0x00
Incorrect table entry
N
Module at position n (n = 1...63) is not supported
Status
Description
Argument
0xFF
At least one module cannot interpret an internal bus
command
0x00
A data fault or a internal bus interruption exists behind the
controller
n
An internal bus interruption exists behind module n
n
Fault during register communication with module n
• 93
Diagnostics