Inputs/Outputs
Analog sensor
0–50 psi represented by a
4–20 mA signal
0–50 psi represented by a
0–20 mA signal
If the sensor's output range does not match your meter's hardware limits, you must calculate the
full scale and/or zero scale values by analyzing the system.
See ION Reference, available from www.usa.siemens.com/pds, for detailed information about the
Analog Input Module.

Configuring option module analog inputs using ION Setup

You can configure analog inputs using ION Setup.
Analog inputs are available on the optional I/O modules.
Calculate your zero scale and full scale values based on the analog source and the input range of
your meter.
Make sure that the analog input port that you want to use is properly configured and connected to
a valid external analog signal source.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Expansion Modules > Option I/O Modules and select the module tab that
corresponds to the option module with the analog input you want to configure.
4. Select the analog input channel and click Edit. Enter the meter password if prompted. The
setup screen for that analog input is displayed.
5. Configure the analog input by selecting the parameter and clicking Edit.
1
Analog I/O option module must have firmware version v1.2 or later.
126
Meter's analog input signal
4–20 mA analog input range
Input value: 12 mA
0–20 mA analog input range
Input value: 12 mA
Parameter
Value/Range
Zero scale
0 to ±10
Full scale
0 to ±10
Port
-
Mode
Voltage, current
Update Rate
One Second/High Speed Defines how frequently the input is updated.
Description
The minimum source value that matches
9
the minimum analog input signal.
The maximum source value that matches
9
the maximum analog input signal.
The physical analog input port connection.
Determines whether the analog input is
monitoring voltage or current.
9410 series - User manual
Analog input register values
Full scale = 50 (psi)
Zero scale = 0 (psi)
Scaled value: 25 (psi)
Full scale = 50 (psi)
1
Zero scale = 0 (psi)
Scaled value: 30 (psi)