Waveform recording

The meter's factory-configured waveform recorders store waveform data related to power quality
events.
Waveform information is used to help identify power system disturbances, which are an
increasing concern for industrial plants, hospitals, data centers and other facilities where the
equipment is sensitive to voltage or current sags, swells, and momentary interruptions. Waveform
information is also used to help ensure compliance with power quality standards.
In addition to measuring and recording numerical values for voltage and current, your meter can
also capture the sinusoidal waveform data. The current and voltage waveform data provides
additional information for analysis of the system's power quality or a power quality event.
When your system's nominal parameters are programmed into the meter, power quality events
such as sags and swells are automatically detected and voltage and current waveform data is
logged. The default factory settings for sag/swell detection are sufficient for most applications, but
you can also modify the amount of deviation from the nominal required to trigger waveform
recording.

Waveform data storage format

Your meter's waveform data storage format is defined by:
• Cycles: the number of cycles included in the waveform (its duration).
• Samples: samples per cycle, which is the number of waveform data points collected in each
cycle.
This gives you the option to record a lot of information for a very short duration or less information
over a longer duration. You can also configure the waveform recording to record pre-event and
post-event data.

Types of waveform data

You can use your meter to detect ITI (CBEMA) - type disturbances, and determine information
regarding the magnitude and duration of each disturbance. This information can be used by your
energy management system to plot the disturbance on an ITI (CBEMA) curve.
COMTRADE waveform data is available from your meter.
NOTE: If you are generating COMTRADE waveform information, the associated waveform
recorders cannot be modified unless COMTRADE is disabled. If the waveform recorders are not
configured identically, COMTRADE waveform information will not be generated.
7EN05-0336-09
Parameter
Log Memory
Log Storage
Description
Information only. This is automatically calculated, and displays
how much memory the log uses based on the Log Interval
and Log Depth
Information only. This is automatically calculated, and displays
how much total memory is left after subtracting the Log
Memory usage
Logging
211

Advertisement

Table of Contents
loading

This manual is also suitable for:

9410 series

Table of Contents