Configuring Advanced Power Quality - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

Power quality
10. Click Next.
11. Configure your meter's COMTRADE settings:
12. Click Finish.
You are returned to the Sag/Swell Logging screen and the entry shows your new
configuration.
If nothing happens when you click Finish, check the log depths and buffer depths for all your
other data logs to make sure that the meter has enough memory for these changes. Adjust
the log depth and buffer depth of the data and waveform recorders if needed.

Configuring Advanced Power Quality

Use to configure your meter's power quality (PQ) monitoring and logging settings for IEC 61000-
4-30, EN 50160, and IEEE 519.
The meter's PQ frameworks are designed with logical dependencies. IEC 61000-4-30 must be
enabled first if you want to monitor and record PQ parameters for EN 50160 or IEEE 519.
DATA LOSS
Failure to follow these instructions can result in data loss.
• Enable IEC 61000-4-30 before enabling other power quality monitoring and recording
features.
• Enable Sag/Swell before configuring power quality disturbance related features.
To configure Advanced Power Quality:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Power Quality > Advanced PQ.
188
NOTE: The maximum number of cycles (pre-event + post-event) cannot exceed the total
number of cycles in the waveform format.
a. Select or clear the Generate COMTRADE files check box to enable or disable the
creation of COMTRADE records.
NOTE: The waveform viewer on your meter's webpages uses the meter's
COMTRADE files. If you want to view waveforms on the meter's webpages, select
Generate COMTRADE files.
NOTE: The factory-default configuration for COMTRADE only supports Standard
waveform capture.
b. Set the Log depth for the COMTRADE files to specify the maximum number of records
stored on your meter's SFTP site.
NOTICE
9410 series - User manual
7EN05-0336-09

Advertisement

Table of Contents
loading

This manual is also suitable for:

9410 series