Analog Inputs (Meter Ordering Option): AI1 to AI4

AI3
+ -
AI4 AI3 AI2 AI1

Analog Outputs (Meter Ordering Option): AO1 to AO4

AO3
OUT COM
AO4 A03 A02 AO1
Type
Wire
Signal Type
Available Options
Input Impedance
Accuracy
Update Rate
Isolation to Ground
Isolation Impedance
Thermocoupler
N
OTE
Do not connect the analog inputs of the I/O card to the analog outputs on
the same I/O card.
Type
Wire
Signal Type
Available Options
Driving Capability
Accuracy
Update Rate
Latency
Isolation to Ground
+
Analog
Meter
N
OTE
Do not connect the analog outputs of the I/O card to the analog inputs on
the same I/O card.
Captured wire connector
2
1.3 to 0.1 mm
DC current
0 to 20 mA (scalable 4-20 mA) or 0 to 1 mA
24 Ω (0-20 mA option) or 475 Ω (0-1 mA option)
+/– 0.3% of full scale
1 s
750 V
max 400 kΩ (channel/channel)
mA
mV
Voltage-to-
Current
Transducer
Captured wire connector
2
1.3 to 0.1 mm
DC current
0 to 20 mA (scalable 4-20 mA) or -1 to 1 mA
(scalable 0-1 mA)
500 Ω (0-20 mA option) or 10 kΩ (-1 to 1 mA
option)
+/– 0.30% of full scale
½ cycle or 1 s
min. 1 cycle for measurement + ½ cycle for ION
+ 1 s delay for hardware
750 V
Meter
OUT
AO1
COM
(16 to 28 AWG)
Meter
Example
+
application:
temperature
AI1
sensing
-
(16 to 28 AWG)
Example application: driving an
analog meter with the DC
current output
11