Accuracy Verification Test Points - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

Verifying accuracy
• Inadequate meter control power, resulting in the meter resetting during the test procedure.
• Ambient light interference or sensitivity issues with the optical sensor.
• Unstable power source causing energy pulsing fluctuations.
• Incorrect test setup: not all phases connected to the reference device or the energy standard.
All phases connected to the meter under test should also be connected to the reference
meter/standard.
• Moisture (condensing humidity), debris or pollution present in the meter under test.

Accuracy verification test points

The meter should be tested at full and light loads and at lagging (inductive) power factors to help
ensure testing over the entire range of the meter.
The test amperage and voltage input rating are labeled on the meter. Refer to the installation
guide or data sheet for your meter's nominal current, voltage and frequency specifications.
Watt-hour test point Sample accuracy verification test point
Full load
Light load
Inductive load
(lagging power
factor)
VAR-hour test point Sample accuracy verification test point
Full load
Light load
Inductive load
(lagging power
factor)
268
100% to 200% of the nominal current, 100% of the nominal voltage and
nominal frequency at unity power factor or one (1).
10% of the nominal current, 100% of the nominal voltage and nominal
frequency at unity power factor or one (1).
100% of the nominal current, 100% of the nominal voltage and nominal
frequency at 0.50 lagging power factor (current lagging voltage by 60°
phase angle).
100% to 200% of the nominal current, 100% of the nominal voltage and
nominal frequency at zero power factor (current lagging voltage by 90°
phase angle).
10% of the nominal current, 100% of the nominal voltage and nominal
frequency at zero power factor (current lagging voltage by 90° phase
angle).
100% of the nominal current, 100% of the nominal voltage and nominal
frequency at 0.87 lagging power factor (current lagging voltage by 30°
phase angle).