4.10.1 ANALOG OUTPUT SETUP

FUG1010GCN provides current, voltage and pulse-rate analog outputs. [Analog Output Setup] allows
you to assign data functions for these signals. The computer's terminal strip contains the analog output
terminals.

System 1010 Analog Outputs

Io (Isolated current)
Vo (DC voltage)
Pgen (TTL logic)
Digital Pgen*
*Digital Pgen replaces Pgen in Custody Transfer FUG1010GCCDN flowmeters.
Analog Out Setup Data Categories (for Dual Channel flowmeter)*
Vfo
Vfo2
Vfab
Vs
Valc
Vtrb
Vsg
Base S.G.
Viscosity
T1
Iin1, Iin2, Iin3, Iin4
*Dual Path meters have the data categories listed above plus characters 1 (Path 1), 2 (Path 2) and S (System).
** See paragraph 4.3 Gas Parameters Menu to set Base Temp F or C.
NOTE: For Expanded I/O Modules, refer to drawing 1010N-7-7 and addendum 1010FMA-14 for
details.
Model Number and I/O Module
FUG1010GCN
FUG1010GCN with 1010N-7 Expanded I/O Module
FUG1010GCDN
FUG1010GCDN with 1010N-7 Expanded I/O Module 1010N-7-7 (Sheet 2 of 3)
FUG1010GCCDN

Assigning Io Output Functions

The Io analog output is a self-powered, isolated 4-20mA DC signal that varies linearly in relation to a se-
lected data function. Some models feature auxiliary current outputs that are loop powered.
CAUTION: Do not connect self-powered Io outputs to a powered loop.
The flowmeter's 4-20 mA outputs (except for the Auxiliaries provided in certain A-option models of the
FUG1010GCN flowmeter) provide a "Fault" indication by dropping to approximately 2 mA when the
flowmeter's primary sensing mechanism is unable to measure the flowrate and fault is declared. This
fault current is generated regardless of the variable currently selected for that output.
4 to 20 mA varies in proportion to an assigned data function.
0 to 10 Vdc varies in proportion to an assigned data function.
0 to 5000 Hz varies in proportion to an assigned data function.
User selective pulses per unit flow.
Spanned volumetric/mass flow rate
Additional spanned volumetric/mass flow rate
Spanned unsigned flow magnitude
Spanned liquid sonic velocity
Receive signal amplitude
Relative degree of gas turbulence
Spanned specific gravity
Spanned SG referenced to user temperature**
Gas viscosity in centistoke units
Current gas temperature
Represents a re-transmit of the analog input signals (e.g., Pressure and
Temp inputs can be transmitted on the 4/20 mA output).
Table To Determine Proper I/O Installation Drawings
Installation Drawing and Page Number
1010N-2-7 (Sheet 2 of 2)
1010N-7-7 (Sheet 2 of 3)
1010N-2-7 (Sheet 2 of 2)
1010N-7-7 (Sheet 3 of 3)
4-57
1010GCNFM-3C