Configuring Led Energy Pulsing Using Ion Setup - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

9410 series - User manual
NOTE: To modify your default energy source value, go into the advanced mode of ION Setup
and modify the associated Calibration Pulser module. This is an advanced procedure that
should only be performed if you have advanced knowledge of ION and the power system your
meter is connected to.
See ION Reference, available from www.usa.siemens.com/pds, for more information.
See
"Alarm and status LED indicators" on page 157
Configuring LED energy pulsing using ION Setup
You can configure your meter's energy pulsing LEDs for energy pulsing using ION Setup.
1. Start ION Setup.
2. Open the Setup Assistant for your device.
3. Select LED pulsing.
4. Select the tab that corresponds to the energy pulsing LED you want to configure.
5. Configure the following basic parameters for your meter's energy pulsing LEDs.
Energy pulsing LED parameters available through ION Setup
Parameter
Source
Enable
Int Mode
Kt
Pulse Width
Pulser Mode
Pulse ovrld
NOTE: To perform specialized configuration go into the advanced mode of ION Setup and
modify, disable or add a new Calibration Pulser module. These are advanced procedures that
should only be performed if you have advanced knowledge of ION and the power system your
meter is connected to.
7EN05-0336-09
Description
Link this input to the value that you want to pulse on the LED.
Configuring this setting should only be performed by users with advanced
knowledge of ION, the device template and the power system the device is
connected to.
Specifies the integration mode for the LED (forward, reverse, absolute or
net).
The amount of source energy required to make the LED pulse.
The minimum time in seconds between LED pulse transitions.
Select when the energy pulsing LEDs will pulse:
• Always: the energy pulsing LEDs are always pulsing based on their
energy source value.
• Test Only: the energy pulsing LEDs turn off and will not pulse.
Pulsing normally indicates that the energy pulsing LED should be operating
normally.
Pulsing suspended indicates that the energy pulsing LED is not able to pulse
quickly enough. Modify the Kt value to decrease the number of energy pulses
or decrease the pulse width, if supported by the device collecting pulses.