Environmental Characteristics; Leds - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

9410 specifications
Response time
Minimum pulse width
Current draw
Voltage ON state
Voltage OFF state
IRIG-B

Environmental characteristics

Operating temperature
Storage temperature
Humidity rating
Pollution degree
Altitude
Location/mounting
Maximum operating temperature with option modules
Maximum operating
temperature
70 ºC (158 ºF)
70 ºC (158 ºF)
60 ºC (140 ºF)

LEDs

Energy pulsing LEDs (visible and infrared) located on top of meter
Type
Wavelength
Maximum pulse rate
274
20 ms
20 ms
ON: ≤ 2.5 mA
OFF: ≤ 0.5 mA
4–30 V AC/4–60 V DC
0–1.4 V AC/0–2.0 V DC
IRIG-B00x format (unmodulated IRIG-B time code)
Coded expressions 0 to 7 are supported but the year data is
not used.
–25 ºC to Max temp (–13 ºF to Max temp)
Note:
Maximum operating temperature could change based on the
quantity and type of attached option modules. See Maximum
operating temperature with option modules below.
–40 °C to 85 °C (–40 °F to 185 °F)
5%–95% RH non-condensing
Maximum dewpoint: 37 °C (99 °F)
2
< 3000 m (9843 ft) above sea level
Not suitable for wet locations
For indoor use only
Must be permanently connected and fixed
948M2DO6DI
Digital (2 out, 6 in)
0–4
0
1, 2
Visible orange, infrared
600–609 nm (orange), 825–925 nm (infrared)
< 25 Hz (based on line frequency)
9410 series - User manual
948M2AO4AI
Analog (2 out, 4 in)
0,1
2
2–4
7EN05-0336-09

Advertisement

Table of Contents
loading

This manual is also suitable for:

9410 series

Table of Contents