Snmp Implementation - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

9410 series - User manual
3. Configure your meter's SNMP parameters by selecting the parameter value.
4. Click Apply to configure the meter's SNMP parameters.

SNMP implementation

MIB files
Your meter is compliant with MIB-II as defined by the standard MIB file RFC 1213.
7EN05-0336-09
Parameter
Enable SNMP
SNMP Port Number
System contact
System name
System location
Read-only Community
Name
Read-write Community
Name
Enable SNMP Traps
Enable High Priority
Alarms
Enable Med Priority
Alarms
Enable Low Priority
Alarms
Report Buffer Size
Report Hold Time
Trap Rcvr1 Addr to Trap
Rcvr4 Addr
Range
Description
Yes/no
Enables or disables SNMP on your meter.
161 (default)
Enter your meter's SNMP port number.
Enter the name of your SNMP system
-
administrator.
-
Enter a descriptive name for your meter.
-
Enter your meter's location.
Enter the community string used for SNMP
-
get (read-only) requests.
Enter the community string used for SNMP
set (read/write) requests. NOTE: You can
-
use the read/write community string for
SNMP get (read-only) requests.
Enables or disables SNMP trapping on your
Enable/disable
meter.
Enables trapping of events that create high
Yes/no
priority alarms.
Enables trapping of events that create
Yes/no
medium priority alarms.
Enables trapping of events that create low
Yes/no
priority alarms.
Enter the maximum number of trap
messages to be stored before the trap
1–30
messages are sent. Traps are sent when
the number of trap messages is equal to or
greater than this value.
Enter the maximum duration for trap
messages to be held. Trap messages are
1–300 seconds
sent when the time after a trap event has
occurred is equal to or greater than this
value.
Enter up to four trap receiver IP addresses,
-
where trap messages will be sent.
Communications
113