Alarm Indicators - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

Alarms and alerts
Alarm priority
High (red)
Medium (yellow)
Low (blue)
Info Only (no alarm)*
None (no alarm or event)* 0
* Alarms with priority of Info Only or None are not indicated or displayed.
Info Only and None event priority
Alarms with a priority of Info Only or None are not shown on the meter's display, and do not
function as alarms. If the alarm's priority is set to Info Only, and the event priority is greater than
the event log cutoff value, the associated event is recorded in the meter's event log. If the alarm's
priority is set to None, the event priority is automatically set to zero, and no associated event is
logged in the meter's event log.
For events that you want to log for future reference or troubleshooting, but don't want alarm
functions, set the alarm priority to Info Only.
For nuisance events that frequently occur, and you have no desire to log for reference or
troubleshooting, set the alarm priority to None.

Alarm indicators

Your meter's display has an alarm indicator to show you what alarm levels have been detected
(active or historic) and whether they have been acknowledged.
For active high priority alarms, the display will also flash until the alarm is acknowledged. There is
also an alarm LED to indicate the meter's alarm condition.
Alarm
Active high
Active medium
Active low
172
Event priority
192–255
128–191
64–127
1–63
Alarm icon
Alarm icon flash Alarm LED
Flash if not
Red solid bell
acknowledged
Yellow solid
Flash if not
bell
acknowledged
Flash if not
Blue solid bell
acknowledged
9410 series - User manual
Display
• Flash if not
acknowledged
Flash if not
acknowledged
• Steady if
acknowledged
• Flash if not
acknowledged
No flash
• Steady if
acknowledged
• Flash if not
acknowledged
No flash
• Steady if
acknowledged
7EN05-0336-09