Installation and commissioning
3. Configure the parameters in Metering Setup > Advanced, if appropriate.
Advanced tab
Using the Phasor Viewer
Phasor diagrams can help verify or troubleshoot issues with voltage and current input wiring.
Use ION Setup's Phasor Viewer to display a real-time phasor diagram of the voltage and current
input signals.
To use the Phasor Viewer:
1. Start ION Setup and open the Setup Assistant for your meter.
2. Click Metering Setup > Phasor.
3. Select Phasor Viewer and click Show.
4. To change the polarity of the voltage or current inputs, click Show Setup to display the
Polarity Settings.
Select the box beside the input you want to invert polarity, then click Apply to Meter.
Basic setup using the webpages or display
You can use the meter webpages or display to configure basic metering parameters.
61
Parameter
Values
Nominal
1–999,999
Voltage
Nominal
1–999,999
Current
Nominal
50, 60
Frequency
Parameter
Values
PhaseOrder
ABC, ACB
I4 Prim
1–999,999
I4 Sec
1–999,999
Scale Rev
ON, OFF
Param
Description
Nominal voltage (V) used for metering functions
such as harmonic calculations and sag/swell
detection
Nominal current (A) used for metering functions
such as harmonic calculations and sag/swell
detection
Nominal frequency (Hz) used for metering
functions such as alarms
Description
Power system's rotation order of voltage
phases
I4 current transformer's primary winding
current rating
I4 current transformer's secondary winding
current rating
Specifies whether revenue readings are
presented as primary or secondary side values
(ON = primary side, OFF = secondary side)
9410 series - User manual
7EN05-0336-09