Snmp Trapping; Configuring Snmp Using Ion Setup - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

9410 series - User manual
A
Trap receivers
B
SNMP agent (meter)
C
NMS with SNMP manager software and MIB file installed
NOTE: The NMS computer can also function as a trap receiver.

SNMP trapping

SNMP trapping allows your meter's agent to notify the NMS of events with an unsolicited SNMP
message (a "trap" of the meter's alarm event).
You can enter up to four IP addresses for SNMP trap notification for generic and enterprise-
specific traps. For enterprise traps, you must also define the number of events or maximum time
delay before SNMP traps are sent to the NMS.
SNMP trapping is only supported on SNMP v2.

Configuring SNMP using ION Setup

You can enable SNMP and configure SNMP trapping using ION Setup.
Download the ION MIB file from www.usa.siemens.com/pds.
To configure SNMP using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Communications > Advanced Ethernet > SNMP.
7EN05-0336-09
Communications
111

Advertisement

Table of Contents
loading

This manual is also suitable for:

9410 series

Table of Contents