• The oldest COMTRADE record is overwritten by the newest record when the COMTRADE
depth is exceeded.
NOTE: COMTRADE files can only be downloaded using an Ethernet connection. They cannot
be downloaded using serial, modem or Ethernet gateway connections.
See the COMTRADE and ION technology technical note, available from
www.usa.siemens.com/pds, for details.

Waveforms on the meter webpages

You can use the waveform viewer on the meter's webpages to view waveforms generated as a
result of power quality events.
Set up the meter to view waveforms on the webpages
Before you can view waveforms on the meter's webpages, you need to perform some basic
configuration to enable waveform capture and store the waveforms in COMTRADE format.
1. Enable waveform
capture on your meter
Set the meter's nominal
voltage using ION Setup or
meter webpages.
The waveform viewer uses the meter's COMTRADE files to display the waveforms. If the events
you want to capture are not included in the default framework, you can customize the meter's
waveform recording framework.
Webpage waveform viewer
After COMTRADE files are generated by your meter, you can view them using the waveform
viewer.
196
2. A waveform is captured when
a power quality event occurs
A COMTRADE record is
generated and saved to your
meter's internal SFTP site.
9410 series - User manual
3. View the waveform on the
meter's webpages
Go to the waveform viewer
(Monitoring > Waveforms) to
explore the waveform data.
7EN05-0336-09