Configuring time information using ION Setup

You can set the time and date and configure the time synchronization settings using ION Setup.
NOTE: The clock screen is where you set the start day of the week for the time of use feature.
NOTE: You must manually adjust the date and time information if the device is installed in a
different time zone location from the computer running ION Setup.
1. Start ION Setup.
2. Open the Setup Assistant for your device.
3. Click Clock > Timezone tab.
4. Select any parameter and click TimeSync to synchronize your device's date and time with
the computer that is running ION Setup.
5. Click DST Settings to modify your meter's daylight savings time start and end dates, if
required.
6. Select the parameter that you want to configure and click Edit. Enter the password if
prompted.
7EN05-0336-09
Parameter
Value
TimeZone
Time Sync
UTC or LOCAL
Type
Description
Sets the timezone based on the timezones
available from the computer's operating system.
NOTE: This is also where you can synchronize
your meter's DST settings with the computer's.
Specifies the time format of the time sync
message.
UTC (Coordinated Universal time) is equivalent to
Greenwich Mean Time (GMT).
LOCAL is the local time with DST and time zone
information applied.
For SNTP/NTP and PTP time
synchronization, set the Time Sync Type to
UTC.
Time and timekeeping
227