Inputs/Outputs

Configuring onboard digital inputs using ION Setup

You can use ION Setup to configure your meter's digital inputs.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Onboard I/O > Digital Inputs. The tabs correspond to each digital input. Click on the
tab for the digital input you want to edit.
4. Configure the digital input by selecting the parameter and clicking Edit.
5. After the parameter is configured, click OK to save the setting to the meter.
Parameter
Input Mode
Polarity
Debounce
Assigned Port
EventLog Mode Log Off/Log On
State
* You must also configure your meter's clock to use IRIG-B time synchronization.

Configuring option module digital inputs using ION Setup

You can configure option module digital inputs using ION Setup.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Expansion Modules > Option I/O Modules and select the module tab that
corresponds to the option module with the digital input you want to configure.
130
Value/range
Pulse, KYZ, A/C,
IRIG-B*
Inverting/Non-Inverting
0.000–1.000
Defined by your meter's
hardware
OFF/ON
Description
Specifies how the meter processes the signal:
• Pulse: the meter counts an entire pulse (from
off-on to on-off) as one input.
• KYZ: the meter counts a transition (from off-on
or from on-off) as one input.
• A/C: the meter detects analog signals where the
ON condition is based on the presence of an AC
signal.
• IRIG-B*: the meter detects an IRIG-B time
synchronization signal.
Specifies if the signal from the digital port is inverted
or not inverted.
Specifies how long (in seconds) the signal must
remain in a state to be considered a valid state
change.
Your meter's physical digital input port.
Specifies if events generate log entries.
Indicates the status of the digital input.