Loading Option Module Firmware Using Ion Setup - Siemens 9810 Series User Manual

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

Firmware upgrades

Loading option module firmware using ION Setup

Upload firmware to option modules using ION Setup over an Ethernet connection. Each option
module must be upgraded individually.
Prerequisites:
• Option module firmware upgrade (.S19) file(s). Go to www.usa.siemens.com/pds to
download upgrade files.
• Option module is connected to the meter.
• Access to meter's internal SFTP site.
Digital and analog outputs may change state during a firmware upgrade. Option modules are
offline during an option module firmware upgrade; they will not communicate to the meter and the
outputs may change state during the upgrade process.
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Do not use this device for critical control or protection of persons, animals, property, or
equipment.
If your meter's option module loses power during firmware upload, the option module will revert to
its original firmware and you will have to reload the firmware file.
To load firmware option module firmware using ION Setup:
1. Obtain the Option Module firmware files (.S19) that you want to load onto your option
module(s). Save the files where they can be accessed by the computer running ION Setup.
2. Start ION Setup.
3. Open the Setup Assistant for your meter.
4. Select the Template screen.
5. Click the Upgrade tab, then click Upgrade. Enter your meter's password if prompted and
click OK.
6. Navigate to where you have stored the option module firmware. Select the Option Module
firmware file (*.S19) as the file type.
7. Select the option module firmware file and click Open.
An ION Setup window will open. Click Yes to confirm the firmware upgrade.
8. The Option Card Upgrade window opens. Select the Slot that corresponds to the Option
Module type. You can select multiple slots for the same option module type.
9. Click Start.
A dialog box describes the firmware upgrade progress, verifies the firmware, and finishes
with an overview stating whether the firmware was successfully uploaded.