Siemens 9810 Series User Manual page 273

Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

9410 series - User manual
Control power
AC control power
Operating range
Burden (meter only)
Burden (fully optioned meter)
Ride-through time (no optional
accessories)
DC control power
Operating range
Burden (meter only)
Burden (fully optioned meter)
Ride-through time
Low-voltage DC control power
DC control power
Operating range
Burden (fully optioned meter)
Digital output (Form A)
Number
Type
Maximum load voltage
Maximum load current
ON resistance
Signal type
Pulse frequency
Digital inputs
Number
Type
Event timestamp accuracy
Maximum voltage
Pulse frequency
7EN05-0336-09
50/60 Hz ± 10%: 90–415 V ± 10%
400 Hz: 90–120 V ± 10%
max: 7.2 W/18 VA @ 415 V (45–65 Hz)
max: 4.5 W/8 VA @ 120 V (400 Hz)
max: 18 W/36 VA @ 415 V (45–65 Hz)
max. 18 W/28 VA @ 120 V (400 Hz)
100 ms (6 cycles at 60 Hz) min., any condition
200 ms (12 cycles at 60 Hz) typ., 120V AC
500 ms (30 cycles at 60 Hz) typ., 415 V AC
110–415 V DC ± 15%
max. 6 W at 300 V DC
17 W at 300 V DC
100 ms (6 cycles at 60 Hz) min., any condition
20–60 V DC ± 10%
max: 17 W at 18–60 V DC
1
Form A solid-state
30 V AC/60 V DC
75 mA
13–40 Ω at 25 °C (77 °F)
Continuous or pulse
≤ 25 Hz
3
Externally excited, polarity independent
± 1 ms
30 V AC/60 V DC
≤ 25 Hz
9410 specifications
273

Advertisement

Table of Contents
loading

This manual is also suitable for:

9410 series

Table of Contents