Manual Defrost Of Hp / Reset - Siemens Albatros2 User Manual

Heat pump controller
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

Manual defrost of HP / reset

Manual defrost of HP
HP reset
40/221
Siemens Switzerland Ltd
HVAC Products
The RESET button triggers different functions, depending on the number of
seconds the button is kept depressed.
When kept depressed for more than 3 seconds, the manual defrost function
is activated.
Pressing the button for less than 3 seconds triggers a reset.
If an air-to-water heat pump is used, you can manually trigger the defrost function for
the evaporator.
After successfully completing defrosting, or on completion of the maximum permissible
defrost time and permitted number of defrost attempts, the heat pump is automatically
released again. For more information on the defrost function, refer to page 116 ff.
Pending error messages from the heat pump are reset with this button. The preset
switch-on delay will be ignored to prevent undesirable waiting times during
commissioning or fault tracing.
This function should not be used in normal operation.
When releasing the button, the reset is made after 2 seconds.
User manual RVS61.843
5 Handling
RESET
CE1U2355en_02
23. November 2007

Hide quick links:

Advertisement

Table of Contents