Self-calibration

When operating voltage is applied, the actuators self-calibrate (fully retracted ➙ fully
extended ➙ setpoint).
Fully retracted
Fully extended
Never intervene manually during self-calibration.
Correct calibration is only possible with valve stroke > 0.05 inch (1.2 mm). Valve stroke
< 0.05 inch (1.2 mm) results in calibration failure.
If calibration fails, the actuator performs another calibration automatically after
10 seconds.
After three failed calibration attempts, the actuator stem remains in the extended
position and the valves are open.
Electrical fail-safe function (for SSC161.35U, SSC131.39U only)
When first connected to power, or after a power failure, the capacitor which stores energy for
the fail-safe function will be charged. This process takes up to 180 seconds. While the
capacitor is being charged, the actuator cannot respond to any control signals.
In the event of a power failure of more than 5 seconds, the actuator will return to its fail-safe
position within 30 seconds.

Manual operation

A 3-mm Allen wrench can be used to move the actuator to any position.
To move the actuator stem manually
1. Open the cover using a proper screwdriver.
2. Press and hold down button (a) illustrated below for at least three seconds.
Siemens
Smart Infrastructure
Calibration
Power
On
– The actuator ignores any control signal from the controller.
t
Y
CAUTION
NOTICE
7
A6V12681517_enUS_a
02/09/2023