Parameter reference (LUI)
9.2 Setup (2.)
Standard Flow Log Setpoint (2.10.4.4.)
Sets standard flow setpoint as a percent based on flow log mode, when Flow Log Mode
(2.10.4.1.) (Page 215) set to a variable rate.
Values
Rapid Flow Log Interval (2.10.4.5.)
Sets rapid flow log interval in minutes, when Flow Log Mode (2.10.4.1.) (Page 215) set to a
variable rate.
Values
Rapid Flow Log Setpoint (2.10.4.6.)
Sets rapid flow setpoint as a percent based on flow logger mode, when Flow Log Mode
(2.10.4.1.) (Page 215) set to a variable rate.
Values
9.2.10.5
Delete Logs (2.10.5.)
Select YES to permanently delete all data logs in the LUT400.
Options
9.2.11
Other Control (2.11.)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
9.2.11.1
Elapsed Time Relay (2.11.1.)
This function drives a relay based on an interval and duration of time. The relay toggles on
and off at a rate set by the parameters below. (This relay is not affected by LOE, faults,
alarms, or any other condition within the device.)
216
Range: 0.000 to 110.000
Default: 0.000
Range: 1 to 1440
Default: 1
Range: 0.000 to 110.000
Default: 0.000
NO
YES
Operating Instructions, 04/2021, A5E33329501-AG
SITRANS LUT400