Chapter 5: Technical specifications
Table 40: Control panel current consumption specifications (EN 54-4) [1]
Min. current consumption (Imin) [2]
Two-zone control panels
Four-zone control panels
Eight-zone control panels
Max. current consumption in standby (Imax a)
Two-zone control panels
Four-zone control panels
Eight-zone control panels
Max. current consumption in alarm (Imax b)
Two-zone control panels
Four-zone control panels
Eight-zone control panels
[1] With a single power source.
[2] No faults, no battery charging, with standard resistive EOL.

Mechanical and environmental specifications

Table 41: Mechanical specifications
Cabinet dimensions (no cover)
Two- and four-zone control panels
Eight-zone control panel
Weight without batteries
Two- and four-zone control panels
Eight-zone control panel
Number of cable knockouts
Two- and four-zone control panels
Eight-zone control panel
IP rating
Table 42: Environmental specifications
Operating temperature
Storage temperature
Relative humidity
Type class conditions
For detailed cabinet drawings and dimensions, see "Cabinet drawings and
dimensions" on page 84.
82
0.042 A
0.051 A
0.069 A
0.30 A
0.30 A
0.39 A
1.57 A
1.57 A
2.78 A
300 × 97 × 402 mm
421 × 100 × 447 mm
2.8 kg
3.9 kg
14 x Ø 20 mm at top of cabinet
2 x Ø 20 mm at bottom of cabinet
12 x Ø 20 mm at rear of cabinet
20 x Ø 20 mm at top of cabinet
2 x Ø 20 mm at bottom of cabinet
26 x Ø 20 mm at rear of cabinet
IP30
−5 to +40ºC
−20 to +70ºC
10 to 95% noncondensing
3K5 of IEC 60721-3-3