Chapter 3: Configuration and commissioning

Expansion board configuration

Adding an expansion board

Use this menu, available from the basic or advanced configuration menus, to
configure the number of installed expansion boards. The default value is 00.
To add an expansion board:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED flashes fast to indicate that the
module configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The maximum number of expansion boards that can be installed is shown below.
Table 25: Maxumum number of expansion boards
Two- and Four-zone control panels
Eight-zone control panel
[1] Note: For regulatory compliance, when a fire network board is installed, make sure your
configuration does not exceed the usage of three expansion board modules.

Expansion board configuration

Expansion board labels
For configuration purposes expansion boards are labeled A and B (for two- and
four-zone control panels) or A, B, C, and D (for eight-zone control panels).
The label for a given module is defined by its position (left to right) in the control
panel cabinet, The first expansion board installed is module A, the second B, etc.
See your expansion board installation sheet for installation instructions.
Expansion board function and delay configuration
Once an expansion board is installed and added to the control panel
configuration, the following additional configuration options appear on the basic
and advanced configuration menus.
Note:
These configuration options are repeated for each of the installed
expansion boards (A, B, C, and D).
58
Up to two expansion boards
Up to four expansion boards [1]