Sounders silence disabled time

Note:
For control panels in basic evacuation mode, any configured fire sounders
silence disabled time is ignored.
To prevent the immediate silencing of sounders when a fire alarm is first
reported, the Sounder Start/Stop button may be temporarily disabled for a
preconfigured period of time when a configured sounder delay is counting down.
The disable time starts to count down when the control panel enters fire alarm
status and the configured sounder delay starts.
During the configured disable time the Sounder Start/Stop LED is off and the fire
sounders cannot be silenced (before activation) by pressing the Sounder
Start/Stop button.
In the time between the end of the configured disable time and the end of the
configured sounder delay (when the Sounder Start/Stop LED is flashing),
pressing the Sounder Start/Stop button silences sounders (before activation).
A configured sounder delay may still be cancelled while the delay is running (and
sounders activated) by pressing the Sounder Delay button.
Use this menu to configure the time while sounders silence is disabled. The
default setting is 1 minute.
To configure the Sounders Silence Disabled Time:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes fast to indicate that the Sounders
Silence Disabled Time configuration menu is active.
2. Select a delay value from 1 to 10 minutes using the value selection buttons (2
and 4).
3. Press Enter.
4. Save your changes.
48
ZP1-F Series Installation Manual