Ziton ZP1-F2 Installation Manual page 65

Table of Contents

Advertisement

Table 26: Expansion board A configuration options
Display
Description
Module A function
Module A output 1 delay
Module A output 2 delay
Module A output 3 delay
Module A output 4 delay
[1] Available values depend on the type of expansion board installed and the supervision
selected. See Appendix A "Configuration presets" on page 89.
Expansion board function
Use this menu to configure the expansion board function. The default value
depends on panel configuration. For most configurations, the default value is 01.
For two-zone panels, or panels configured for EN 54-13, the default is 05. For the
available presets, see Appendix A "Configuration presets" on page 89.
To configure the expansion board function:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the
ON LED on the expansion board flashes fast to indicate that the module
function configuration menu is active.
2. Select a value from 01 to 92 using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
ZP1-F Series Installation Manual
Chapter 3: Configuration and commissioning
Value
01 to 92 [1]
00 to 10 minutes
00 to 10 minutes
00 to 10 minutes
00 to 10 minutes
59