Advanced configuration

The default password for advanced configuration is 4444. After entering the
password, the first displayed menu is Advanced default configuration (indicating
the advanced installer user level). For more information see "User level
passwords and indications" on page 28.

The advanced configuration menu

Configuration options for this menu are shown in Table 24 below. More
information for each option is included in the related topic.
Note:
All configurable options included in "Basic configuration" on page 33 are
also available from the advanced configuration menu.
Table 24: The advanced configuration menu
Display
Menu
Advanced default
configuration
EN 54-13 supervision
Panel mode
Sounder delay
(or Evacuation sounder
delay for NBN S 21-100
mode)
Sounder operation during a
zone test
Sounder re-sound
Silence sounders disabled
time
ZP1-F Series Installation Manual
Chapter 3: Configuration and commissioning
Values
Configuration presets, as
defined in "Basic default
configuration" on page 35
ON/OFF
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
BS 5839-1 (No 2nd stage)
BS 5839-1 (2nd stage)
NBN S 21-100
NEN 2535
Custom
00 to 10 minutes
ON/OFF
ON/OFF
0 to 10 minutes
Operating mode
All
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
NBN S 21-100
NEN 2535
Custom
All
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
NBN S 21-100
All
All
All
43