Extended fire routing delay

Use this menu to configure an extended fire routing delay of up to 10 minutes in
operating modes where the feature is available.
Default delays
The default extended fire routing delay for each operating mode is shown below.
Table 23: Extended fire routing delay default values
Operating mode
EN 54-2 Scandinavia
NEN 2535
EN 54-2
EN 54-2 Evacuation
BS 5839-1
NBN S 21-100
To configure an extended delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes fast to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
This value must be greater than the configured fire routing delay.
3. Press Enter.
4. Save your changes.
Once configured the delay is enabled at the same time as the standard fire
routing delay.
A steady Fire Routing Delay LED indicates that all configured fire routing delays
are enabled.
Extended fire routing delay operation
The same conditions required to apply a fire routing delay are applicable to apply
an extended fire routing delay (i.e. delay enabled, automatic alarm in a zone with
delays configured, no fire routing inhibit delay input activated, and no input using
the delays off function activated).
If the conditions exist to apply the delay, fire routing and extended fire routing
delays elapse concurrently when a fire alarm event is reported. After an alarm
condition, the fire routing delay is the active delay to activate fire routing.
ZP1-F Series Installation Manual
Chapter 3: Configuration and commissioning
Default delay in minutes
03
03
00
This feature is not available in these operating modes.