En 54-13 Supervision Mode - Ziton ZP1-F2 Installation Manual

Table of Contents

Advertisement

Chapter 3: Configuration and commissioning

EN 54-13 supervision mode

Use this menu to select the zone supervision mode (EN 54-13 supervision
enabled or disabled). By default EN 54-13 zone supervision is disabled.
Note:
EN 54-13 supervision mode is not available in BS 5839-1 mode.
To configure the supervision mode:
1. Set the display as shown below, and then press Enter.
The Sounder and Fire Routing Fault/Disable/Test LEDs and all zone LEDs
flash quickly to indicate that the supervision mode configuration menu is
active.
2. Select the supervision mode using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Default setting. EN 54-13 zone supervision is disabled
and all outputs are configured as Class B.
EN 54-13 zone supervision is enabled and all outputs
are configured as Class A.
36
ZP1-F Series Installation Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zp1-f seriesZp1-f4Zp1-f8

Table of Contents