Chapter 3: Configuration and commissioning

Zone delay

Use this menu to configure zone delays (on or off), for each zone in your fire
alarm system. If the zone delay is ON, for alarms reported from this zone, any
output activation (sounders, fire routing and expansion board outputs) will
consider delay before activation. The default setting for all zones is ON.
For a stand-alone fire panel, you specify the zone using the zone number.
When the control panel is in a fire network, unique zone numbers are created by
defining a unique starting number for the first zone in each panel. For example, if
the first zone is numbered 101, then zone 08 will have the number 108.
In a fire network, if the control panel is configured to activate with remote zones,
you can enter "others" to select the delay for remote zones.
See the topic "Fire network and repeaters configuration" on page 61 for further
details.
To configure the zone delay:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
— or —
Select "others" to select the remote zones.
The Zone alarm LED flashes fast to indicate that the corresponding zone
configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Configured delays are applied when the alarm is
reported from this zone.
Configured delays are not applied. Outputs activate
immediately when the alarm is reported from this zone.
50
ZP1-F Series Installation Manual