Zone configuration

Use this menu to configure zone settings for each zone in your fire alarm system.
The default setting for each operating mode is included in Appendix A
"Configuration presets" on page 89.
To configure the zone:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The Zone fault/test/disable LED flashes fast to indicate that the corresponding
zone configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Passive end-of-line
Active end-of-line [1]
Unlatched (only available in BS 5839-1 mode) [1]
Passive end-of-line with CleanMe [1][2][3]
Active end-of-line with CleanMe [1][2][3]
Intrinsically-safe zone [1][4]
[1] Option not available if EN 54-13 supervision is enabled.
[2] Option not available if operating mode is NEN 2535.
[3] The CleanMe feature is not available for Ziton devices.
[4] By default, even zones are configured as manual and odd zones are set
as automatic.
ZP1-F Series Installation Manual
Chapter 3: Configuration and commissioning
49