Basic default configuration

Use this menu to select common operating mode configuration presets. The
default setting is 01 (EN 54-2, passive end-of-line).
To select an operating mode configuration preset:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
See Table 20 below for descriptions of the presets.
3. Press Enter.
4. Save your changes.
A selected list of operating mode configuration presets is shown below. For a
detailed list of all available configuration presets and characteristics, see
Appendix A "Configuration presets" on page 89.
Table 20: Common operating mode configuration presets (EN 54-13 disabled)
Display
Operating mode
01 (default)
EN 54-2
05
EN 54-2 Evacuation
07
EN 54-2 Scandinavia
11
BS 5839-1
21
NBN S 21-100
31
NEN 2535
The operating mode is indicated by the first digit in the display and the
configuration type by the second digit. If a custom configuration has been applied
(via the advanced configuration menu), then the second digit is a zero, as shown
below.
Display
Configuration
01
EN 54-2 preset configuration
11
BS 5839-1 preset configuration
21
NBN S 21-100 preset configuration
31
NEN 2535 preset configuration
ZP1-F Series Installation Manual
Chapter 3: Configuration and commissioning
Zone end-of-line
Passive
Passive
Passive
Active
Passive
Passive
Display Configuration
00
EN 54-2 custom configuration
10
BS 5839-1 custom configuration
20
NBN S 21-100 custom configuration
30
NEN 2535 custom configuration
Zone type
Mixed
Mixed
Mixed
Mixed
Odd zones: Automatic
Even zones: Manual
Odd zones: Automatic
Even zones: Manual
35