Connecting fire routing equipment to supervised outputs
Connect fire routing equipment as shown in Table 14 below.
Table 14: Connecting fire routing equipment
Operating mode
EN 54-2
EN 54-2 Scandinavia
NEN 2535
Note:
Fire routing in EN 54-2 operating modes makes no distinction between
automatic and manual alarms. If this feature is required, install a 2010-1-SB
expansion board and use separate outputs for each alarm type.
Connecting the fault warning output to external equipment
Caution:
This connection is mandatory to comply with EN 54-2 Clause 8.9 (Fault
Warning Routing Equipment).
Note:
This feature is only available in NEN 2535 mode with a 2010-1-SB
supervised expansion board configured to presets 32 or 35. See "Expansion
board presets" on page 96.
Connect the external equipment to the OUT3 output on the 2010-1-SB
supervised board. The wiring must be returned back to the control panel to the
2010-FS-EOL user supervisory board connected to INPUT2, as shown below.
Figure 9: Connecting to fault warning output
1. 2010-FS-EOL user board
2. Control panel PCB connectors
3. 2010-1-SB expansion board connectors
ZP1-F Series Installation Manual
Output Class
Class B (default)
Class A (EN 54-13)
Class B (default)
Class A (EN 54-13)
Fire routing
(automatic)
OUT4
OUT3, OUT4
OUT3
OUT3, OUT4
Chapter 2: Installation
Fire routing (manual)
OUT4
OUT3, OUT4
OUT4
OUT3, OUT4
17