Chapter 3: Configuration and commissioning
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at Operator user level.
To enable a configured delay:
1. Exit Installer user level.
2. Enter the Operator user level password.
3. Press the Fire Routing Delay button.
A steady Fire Routing Delay LED indicates that the delay is enabled.
Fire routing delay operation
The delay applies to the activation of fire routing (if configured) only if all of the
following are true:
The delay is enabled
The initiating device (detector or manual call point) is installed in an automatic
zone (or the initiating device is a detector installed in a mixed zone)
The initiating device is configured in a zone with delays configured (by
default)
A fire routing inhibit delay input is not activated (if configured)
Any input using the delays off function must not be active
If the delay is not enabled, the control panel activates fire routing (if configured)
immediately after the detection of the fire alarm.
40
ZP1-F Series Installation Manual