Chapter 3: Configuration and commissioning

Basic configuration options

The following table shows the options for creating basic fire network (firenet)
configurations.
Table 27: Basic configuration options for the fire network
Display
Description
Firenet identifier for the panel
(the panel node number in the
network)
Firenet number of nodes (the
number of nodes in the
network) [1]
Firenet initial zone number [2]
— or —
Firenet initial panel number to
be repeated [2]
[1] Basic configuration uses consecutive numbers beginning with 1 and ending with the number
entered here. Advanced configuration allows the use of specific, nonsequential node numbers.
When the system has an advanced, custom pattern of node numbers, the displayed value for nn
is "Cu".
[2] Depending on the advanced setting Firenet repeater type (nr), this setting configures the initial
zone repeated or the initial panel repeated.
A basic fire network is either a panel and a repeater, or a 16-zone virtual panel
composed of two 8-zone panels.
To configure a basic fire network:
1. Activate networking by selecting the node number in the fire network.
The value of nI changes from 0 to 1 for the control panel, and from 0 to 2 for
the repeater panel.
If nI is not 0 (networking activated), a network fault is reported if the network
card is not present.
The Network Fault LED blinks every 10 seconds to indicate that the panel is
connected to the network without faults.
62
Value
00 to 32
00 = Stand-alone (no networking)
Default: 00
02 to 32
Default: 02
0001 to 9999
The number has four digits. Identified by position,
these are: 1234.
Press Up to enter the first two digits of the
number (positions 1 and 2).
Press Down to enter the last two digits of the
number (positions 3 and 4).
01 to 32
Default: 01
ZP1-F Series Installation Manual