Chapter 3: Configuration and commissioning

Advanced configuration options

The following table shows the options (available to an advanced configuration
user) for creating an advanced fire network configuration.
Table 28: Advanced configuration options for the fire network
Display
Description
Firenet identifier
Firenet number of nodes [1]
Firenet initial zone number when
the firenet repeater type (nr) = 2n
— or —
Firenet initial panel number to be
repeated when the firenet
repeater type (nr) = Pn
Firenet global controls
Firenet loop class
Firenet process remote zones
Firenet repeater type
Firenet map
64
Value
0 to 32
0: Stand-alone (no networking)
Default: 0
2 to 32
Default: 2
0001 to 9999
The number has four digits. Identified by
position, these are: 1234.
Press Up to enter the first two digits of the
number (positions 1 and 2).
Press Down to enter the last two digits of the
number (positions 3 and 4).
01 to 32
Default: 01
On/ OFF
Default: On
A/ B
Default: B
On/ OFF
Default: On
2n = Zones Repeater
Pn = Panels Repeater
Default: 2n
Submenu: 1 – 32
Values: On/OFF
Default: ON for nodes 1 and 2, OFF for the rest