Chapter 2: Installation

Connections

WARNING:
Electrocution hazard. To avoid personal injury or death from
electrocution, do not make any control panel or system connections while the
control panel is connected to the mains power supply.

Recommended cables

Recommended cables for optimal system performance are shown in the table
below.
Table 2: Recommended cables
Cable
Mains cable
Input, output, auxiliary 24V,
relay, expansion board
Zone circuit cable (mixed zone) 12 to 26 AWG (3.31 to 0.13 mm²)
Zone circuit cable (automatic or
manual zones)
Fire network cable
Note:
Other types of cable may be used subject to site-specific EMI conditions
and installation testing.
Use 20 mm cable glands to ensure clean and secure connections at the control
panel cabinet. All cables should be fed through the cable guides in the cabinet
housing to eliminate movement.
8
Cable description
3 x 1.5 mm²
12 to 26 AWG (3.31 to 0.13 mm²)
Twisted-pair (max. 40 Ω / 500 nF)
Twisted-pair (max. 40 Ω / 500 nF)
12 to 26 AWG (3.31 to 0.13 mm²)
Twisted-pair (max. 55 Ω / 500 nF)
Twisted-pair, Cat 5
12 to 26 AWG (3.31 to 0.13 mm²)
Maximum cable length
N/A
2 km
2 km
2 km
1.2 km
ZP1-F Series Installation Manual