Monitoring With Function Code 03 And 04; Table 21 Default Modbus Map Measured Values Of M10X-M - ABB M101 Manual

Interface manual modbus
Table of Contents

Advertisement

DE FAU LT DATA M AP

9.2.3. Monitoring with Function Code 03 and 04

Monitoring of the measured (analogue) values from the individual M10x-M is detailed in the
following table.
Modbus
Function
Code
3
3
3
3
3
3
:
3
3
3
3

Table 21 Default Modbus Map Measured Values of M10x-M

50
Modbus
Device
Modbus Register
Register
Number
Name
40001
1
Phase current L1
%
40002
1
Thermal image
40003
1
Time to trip
40004
1
Time to reset
40005
2
Phase current L1
%
40006
2
Thermal image
:
:
:
Phase current L1
40509
128
%
Thermal image
40510
128
Time to trip
40511
128
Time to reset
40512
128
Format
Remarks
Unsigned Int,
% age L1 Current
2Byte
Used thermal
Unsigned Int, 2
capacity (only
Byte
available if TOL
protection func-
tion is used)
Unsigned Int,
Time before
2Byte
M10x-M will trip
the motor (only
available if TOL
protection func-
tion is used)
Unsigned Int,
Time required be-
2Byte
fore reset allowed
(only available if
TOL protection
function is used)
Unsigned Int,
% age L1 Current
2Byte
Unsigned Int,
Used thermal
2Byte
capacity
:
:
Unsigned Int,
% age L1 Current
2Byte
Unsigned Int,
Used thermal
2Byte
capacity
Unsigned Int,
Time before
2Byte
M10x-M will trip
the motor
Unsigned Int,
Time required be-
2Byte
fore reset allowed
1TG C 9 0 8 0 0 4 M 0 2 0 1
DATA M A P PI NG