Setting Frequency Reference Using Pulse Train Signals
When b1-01 is set to 4, the pulse train input to control circuit terminal RP is used as the frequency reference.
Set H6-01 (Pulse Train Input Function Selection) to 0 (frequency reference), and then set the 100% reference
pulse frequency to H6-02 (Pulse Train Input Scaling).
Pulse Input Specifications
Low level voltage
High level voltage
Heavy duty
Pulse frequency
Fig 6.7 Frequency Reference Using Pulse Train Input

Using Multi-Step Speed Operation

With SYSDRIVE 3G3RV series Inverters, you can change the speed to a maximum of 17 steps, using 16 fre-
quency references, and one jog frequency reference.
The following example of a multi-function input terminal function shows a 9-step operation using multi-step
references 1 to 3 and jog frequency selection functions.
Related Parameters
To switch frequency references, set multi-step speed references 1 to 3 and the jog reference selection in the
multi-function contact inputs (any of the terminals S3 to S8). Setting examples are shown below. The unused
terminals need not be set.
Multi-function Contact Inputs (H1-01 to H1-06)
Parameter
Terminal
Number
S5
H1-03
S6
H1-04
S7
H1-05
S8
H1-06
Combination of Multi-Function References and Multi-Function Contact Inputs. In the Above
Setting Example
You can change the selected frequency reference by combining the ON/OFF status of S5 to S8 (multi-function
contact input terminals) to set multi-step speed references 1 to 3 and the jog frequency selection. The follow-
ing table shows the possible combinations.
0.0 to 0.8 V
3.5 to 13.2 V
32 kHz max.
30 to 70%
0 to 32 kHz
Pulse input
Set Value
Multi-step speed reference 1 [Also used for master speed/auxiliary speed switching when
3
multi-function analog input H3-09 or H3-05 is set to 2 (auxiliary frequency reference).]
Multi-step speed reference 2
4
[Also used for auxiliary frequency reference 2 when multi-function analog input H3-09 or
H3-05 is set to 3 (auxiliary frequency reference 2).]
5
Multi-step speed reference 3
6
Jog frequency selection (given priority over multi-step speed reference)
Inverter
3.5 to 13.2 V
RP(Pulse train input termi-
nal)
AC (Analog common)
Details
Frequency Reference