Creating a Project File
The following description provides information about how to create a project file to send the RUN command
and frequency references to three Inverters and read the Inverter status. ("PST" indicates the WS01-PSTF1-J
Protocol Support Tool.)
First, select from I/O items, monitor items, and parameters the data to be exchanged according to the applica-
tion. Then consider what sequence is required by using the protocol macro function.
Example: Writes control input items (such as the RUN command and multi-function input) of the Inverter and
frequency reference, monitors the control output (such as error output and RUN output) of the Inverter, and
monitors the Inverter status.
Three Inverters with Slave addresses from 01 to 03 are installed for communications.
Checking the Register Numbers
In the above example, the following three registers are required.
Control Input: Register 0001 Hex for RUN command
Frequency Reference: Register 0002 Hex
Control Output: Register 002C Hex for Inverter status
Memory Allocations
The PMCR instruction sends each Slave the data in consecutive words specified by the operand and beginning
with the first word (S), and writes in the memory area beginning with the first word (D) the data received.
The following memory allocations are made in the above example.
PMCR
-126
6
C1
C1
C2
C2
S
D
SYSMAC CS or CJ-series Programmable Controllers
Control data
Serial port
Communications Board/Unit
Communica-
tions port
number designation
Port 1: 1 Hex
0 to 7 Hex
Inner Board: E1 Hex
Port 2: 2 Hex
CPU Bus Unit: Unit No. 10 Hex
Sequence No.
0000 to 03E7 Hex 000
Word
Data
Number of data items sent in accordance with
S
PMCR instruction 000B
S 1
No. of Slaves 0003
S 2
First Slave address 0001
S 3
RUN command to Slave 1
S 4
Frequency reference to Slave 1
S 5
Second Slave address 0002
S 6
RUN command to Slave 2
S 7
Frequency reference to Slave 2
S 8
Third Slave address 0003
S 9
RUN command to Slave 3
S 10
Frequency reference to Slave 3
Number of data items received in accordance with
D
PMCR instruction 0003
D 1
Slave 1 Inverter status
D 2
Slave 2 Inverter status
D 3
Slave 3 Inverter status
Communications
Board/Unit
999
RS-422A
/485
SYSDRIVE
3G3RV