Omron SYSDRIVE RV Series User Manual page 78

High-function general-purpose inverters
Table of Contents

Advertisement

PG power
supply +12 V
A-phase pulse
input
B-phase pulse
input
Wiring the 3G3FV-PPGD2
Wiring examples are provided in the following illustrations for the 3G3FV-PPGD2.
Three-phase 200
VAC (400 VAC)
-40
2
When connecting to a voltage-output-type PG (encoder), select a PG that has an output impedance with
a current of at least 12 mA to the input circuit photocoupler (diode).
The pulse monitor dividing ratio can be changed using parameter F1-06.
A-phase pulses
B-phase pulses
Fig 2.31 I/O Circuit Configuration of the 3G3FV-PPGB2
Inverter
Shielded twisted-pair wires must be used for signal lines.
Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
The length of the pulse generator's wiring must not be more than 50 meters.
Fig 2.32 3G3FV-PPGD2 Wiring
A-phase
pulses
B-phase
pulses
3G3FV-PPGD2
Power supply +12 V
Power supply 0 V
Power supply +5 V
Pulse input + (A/B phase)
Pulse input - (A/B phase)
Pulse monitor output
A-phase pulse
monitor output
B-phase pulse
monitor output
E6B2-CWZ1X