"A" Group: Standard Functions
!Tip
3-5-3
Multi-speed and Jog Frequency Setting
Func.
Code
to
96
occurs, the filter naturally has a delayed response. Due to the deadband fea-
ture (
=
), the final output changes only when the 30-sample average
moves past the deadband threshold.
The deadband feature is useful in applications that requires a very stable out-
put frequency but use an analog input for the speed reference. Example appli-
cation: A grinding machine uses a remote potmeter for operator speed input.
After a setting change, the grinder maintains a very stable speed to deliver a
uniform finished surface.
=
A016
31
Hz
Output freq.
reference
+0.1
16-sample avg.
0
-0.1
Analog input
Multi-speed - The MX2 inverter has the capability to store and output up to
16 preset frequencies to the motor (
minology, we call this multi-speed profile capability. These preset frequencies
are selected by means of digital inputs to the inverter. The inverter applies the
current acceleration or deceleration setting to change from the current output
frequency to the new one. The first multi-speed setting is duplicated for the
second motor settings (the remaining 15 multi-speeds apply only to the first
motor).
"A" Function
Name
Multi-step speed selection
Multi-step speed reference 0
2nd multi-step speed reference 0
Multi-step speed reference 1 to 15 Defines 15 more speeds, range
Multi-step speed/position
determination time
Small step change
Threshold exceeded
Deadband
Speed increase given
Noise spikes
to
Description
Select codes:
... Binary operation (16 speeds
selectable with 4 terminals)
... Bit operation (8 speeds
selectable with 7 terminals)
Defines the first speed of a multi-
speed profile, range is 0.00 /
start frequency to 400Hz
= Speed 0 (1st motor)
Defines the first speed of a multi-
nd
speed profile or a 2
motor,
range is 0.00 / start frequency to
400Hz
= Speed 0 (2nd motor)
is 0.00 / start frequency to 400
Hz.
=Speed 1 ~ =Speed15
~
Masks the transition time when
changing the combination of
inputs. Range is 0 to 200
(x10 ms)
Section 3-5
New deadband
). As in traditional motion ter-
Run
Defaults
Mode
EU
Units
Edit
00
-
6.00
Hz
6.00
Hz
0.00
Hz
0.00
0
+0.1
0
-0.1
t