Omron SYSDRIVE RV Series User Manual page 386

High-function general-purpose inverters
Table of Contents

Advertisement

Related Parameters
Param-
eter
Number
Droop con-
trol gain
b7-01
Droop Quan-
tity
Droop con-
trol delay
time
b7-02
Droop Delay
Time
Setting Precautions
Droop control is disabled if b7-01 is set to 0.0.
Set b7-01 to the amount of slip as the percentage of slip when the maximum output frequency is input and
the rated torque is generated.
Parameter b7-02 is used to adjust the responsiveness of droop control. Increase this setting if oscillation or
hunting occur.
Disable the feed forward control (N5-01 = 0) when using the droop control function.
Setting the Droop Control Gain
Set the droop control gain as the speed reduction at a 100% motor torque, as a percentage of the maximum
output frequency.
-178
6
Name
Description
Display
Sets the slip as a percentage
of maximum frequency
when the maximum output
frequency is specified and
the rated torque occurs.
Droop-control is not per-
formed when the setting is
0.0.
Droop control responsive-
ness parameter
When hunting or oscillation
occurs, increase the value.
Torque
0
Fig 6.92 Droop Control Gain
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0.0 to
0.0
Yes
No
100.0
0.03 to
0.05 s
Yes
No
2.00
b7-01
Speed reference
Control Methods
Regis-
V/f
Open
Flux
ter
with
Loop
Vec-
PG
Vector
tor
No
No
A
1CAH
No
No
A
1CBH
100%
Speed

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

3g3rv-v1

Table of Contents