Omron SYSDRIVE RV Series User Manual page 351

High-function general-purpose inverters
Table of Contents

Advertisement

Name
Param-
Description
eter
Display
Number
PID reverse
0: 0 limit when PID output
output
is negative.
selection
1: Reverses when PID
b5-11
output is negative.
Output Rev
0 limit when reverse prohibit
Sel
is selected using b1-04.
0: No detection of loss of
Selection of
PID feedback.
PID feed-
1: Detection of loss of PID
back com-
feedback.
mand loss
Operation continues
detection
during detection, with the
b5-12
malfunctioning contact
not operating.
2: Detection of loss of PID
Fb los Det
feedback.
Sel
Coasts to stop during
detection, and fault
contact operates.
PID feed-
back com-
Sets the PID feedback loss
mand loss
detection level as a percent
detection
b5-13
units, with the maximum
level
output frequency at 100%.
Fb los Det
Lvl
PID feed-
back com-
mand loss
Sets the PID feedback loss
detection
b5-14
detection level in s units.
time
Fb los Det
Time
PID sleep
function
operation
Set the PID sleep function
b5-15
level
start level as a frequency.
PID Sleep
Level
PID sleep
operation
Set the delay time until the
delay time
b5-16
PID sleep function starts in
seconds.
PID Sleep
Time
Accel/decel
time for PID
Set the accel/decel time for
reference
b5-17
PID reference in seconds.
PID Acc/
Dec Time
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 or 1
0
No
A
0 to 2
0
No
A
0 to
0%
No
A
100
0.0 to
1.0 s
No
A
25.5
0.0 to
0.0 Hz
No
A
300.0
*
0.0 to
0.0 s
No
A
25.5
0.0 to
0.0 s
No
A
6000.0
Individual Functions
Regis-
V/f
Open
Flux
ter
with
Loop
Vec-
PG
Vector
tor
A
A
A
1AFH
A
A
A
1B0H
A
A
A
1B1H
A
A
A
1B2H
A
A
A
1B3H
A
A
A
1B4H
A
A
A
1B5H
143