5-6 Operation Functions

RUN Permission Signal

A RUN command is accepted only while the RUN permission signal is ON.
To use this function, allocate "84: ROK" to the multi-function input terminal.
Parameter
C001 to C007
Output frequency
ROK input
RUN command
FW, RV input
5

Multi-step Speed Operation Function (CF1 to CF4, SF1 to SF7)

Multiple RUN speeds can be set in parameters and the applicable speed can be switched
using the terminals.
For multi-step speed operation, either 4-terminal binary operation (with maximum 16 steps) or
7-terminal bit operation (with maximum 8 steps) can be selected.
Parameter
A021 to A035
C001 to C007
5-63
Function name
No.
Multi-function
Input Selection
Function name
No.
Multi-step Speed
A019
Selection
Multi-step Speed 1
A020
Reference 0
Multi-step Speed
References 1 to 15
Multi-step Speed 2
A220
Reference 0
Multi-function Input
Selection
Multi-step Speed/
C169
Position
Determination Time
Data
84: ROK (Permission of RUN
command)
Data
00
4-terminal binary operation with up to
16 variable steps
01
7-terminal bit operation with up to 8
variable steps
0.00, starting frequency to maximum
frequency
0.00, starting frequency to maximum
frequency
0.00, starting frequency to maximum
frequency
02 to 05
Binary operation, 16 steps (CF1 to
CF4)
32 to 38
Bit operation, 8 steps (SF1 to SF7)
0. to 200. (× 10 ms)
Wait time until determination of
terminal input
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Default
Unit
setting
Default
Unit
setting
00
6.00
Hz
0.00
Hz
6.00
Hz
0.
ms