Param-
eter
Number
Alarm oper-
ation selec-
tion during
motor over-
heating
L1-03
Mtr OH
Alarm Sel
Motor over-
heating
operation
selection
L1-04
Mtr OH
Fault Sel
Motor tem-
perature
input filter
time con-
L1-05
stant
Mtr Temp
Filter
-58
5
Name
Description
Display
Set Multi-function input
terminalA3 (H3-05) or A2
(H3-09) to E and select the
operation when the input
motor temperature (ther-
mistor) input exceeds the
alarm detection level [1.17 V
±
5%)].
(
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-
09.
3: Continue operation (H3
on the Operator flashes).
Set Multi-function input ter-
minal A3 (H3-05) or A2
(H3-09) to E and select the
operation when the motor
temperature (thermistor)
input exceeds the operation
detection level [2.34V
±
(
5%)].
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-
09.
Set Multi-function input ter-
minal A3 (H3-05) or A2
(H3-09) to E and set the pri-
mary delay time constant for
motor temperature (ther-
mistor) inputs in seconds.
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 3
3
No
A
0 to 2
1
No
A
0.00 to
0.20 s
No
A
10.00
Regis-
V/f
Open
Flux
Page
ter
with
Loop
Vec-
PG
Vector
tor
A
A
A
482H 6-65
A
A
A
483H 6-65
A
A
A
484H 6-65